30ft CONTAINERISED LOAD BANK & TRANSFORMER PACKAGE
Model 8750 Specifications
A
ELEMENT/FAN MAINTENANCE ACCESS
HV TRANSFORMER (Tx) ACCESS DOOR
LOAD BANK CONTROL ACCESS DOOR
EXHAUST OUTLET FOR Tx COOLING
MAINTENANCE ACCESS
B
2591.0 [102]
B
A
C
5855.0 [230 1
2 ] (TWISTLOCK CENTRES)
2276.0 [89 5 8 ] (MOUNTING BLOCK CENTRES) 2260.0 [89] (TWISTLOCK CENTRES)
PRIMARY HV CABLE ENTRY WITH DIRECT ACCESS TO HV CT's
5880.0 [231 1
2 ] (MOUNTING BLOCK CENTRES)
AIR INLET FOR RESISTIVE ELEMENT COOLING.
120.5 [4 3 4 ]
8922.0 [351 1
4 ] (TWISTLOCK CENTRES)
2438.0 [96]
HV CABLE ACCESS VIA TRANSIT BLOCK SYSTEM SUPPLIED WITH DETACHABLE SHIPPING COVER CUSTOMER TO SUPPLY INDIVIDUAL BLOCKS TO SUIT OWN CABLE SIZES. MORE INFORMATION CAN BE FOUND AT THE SUPPLIERS WEBSITE - www.roxtec.com
8947.0 [352 1
4 ] (MOUNTING BLOCK CENTRES)
218.0 [8 5 8 ]
9125.0 [359 1 4 ]
C
120.5 [4 3 4 ]
120.5 [4 3 4 ]
ADDITIONAL HV CABLE ACCESS
FAN & CONTROL CABLE ACCESS OPENING 242.5x300mm FITTED WITH BLANK ALUMINIUM GLAND PLATE
NOTE: AT LEAST 2 METERS OF CLEAR AREA SHOULD BE LEFT AROUND THE LOAD BANK FOR DOOR OPENINGS AND COOL AIR INLETS
C ( 1 : 30 )
FLOOR ACCESS FOR HV CABLES FITTED WITH BLANK ALUMINIUM GLAND PLATE
A ( 1 : 30 )
1170.0 [46 1 8 ]
B ( 1 : 30 )
3667.5 [144 3 8 ]
300.0 [11 3 4 ]
242.5 [9 1
2 ]
587.5 [23 1 8 ]
3080.0 [121 1 4 ]
400.0 [15 3 4 ]
150.0 [5 7
8 ]
D
400.0 [15 3 4 ]
150.0 [5 7
8 ]
3130.0 [123 1 4 ]
270.0 [10 5 8 ]
716.0 [28 1 4 ]
810.0 [31 7 8 ]
Tx MAINTENANCE ACCESS (IF REQUIRED)
TWISTLOCK FIXINGS AT 20FT PITCH
E
CONTROL CABLE INLET APERTURE CLEAR AREA 400x150mm BLANK ALUMINUM GLAND PLATE
TWISTLOCK FIXINGS AT 30FT PITCH
All dimensions are in millimeters. Specifications subject to change without notice. WEIGHT APPROX - 8750 - 19000kgs
NOTES - ALL LOUVRES ARE MECHANICALLY OPERATED AND WILL OPEN WHEN POWER IS APPLIED TO THE CONTROL CIRCUIT.
REVISION HISTORY
REV
DESCRIPTION
DATE
APPROVED
B
POSITION AND SIZE OF FLOOR APERTURES UPDATED 03/04/2023
MJM
© NJ Froment & Co. Ltd. This document may not be copied or disclosed in whole or partwithout prior written authority.
GENERAL ASSEMBLY 8750 LOAD BANK
CAD Code. Part Number. Drg No.
NJ Froment & Co Ltd Easton on the Hill STAMFORD - PE9 3NP - UK Tel: +44 (0) 1780 480033 avtronpower.com
Drawn - M J Musgrave
Date - 16/11/2021
F
1st Angle Projection
Date -
Checked - Approved -
03756B01
Scale. NTS Dims. mm
Date -
Sheet
1 of 1
Avtron Power Solutions NJ Froment & Co Ltd, Cliffe Road, Easton-on-the-Hill, Stamford, PE9 3NP, UK
www.avtronpower.com customercare@avtronpower.com • +44 (0) 1780 480033 ©2023 Avtron Power Solutions. Publication 5155 • Rev. C
Made with FlippingBook - Online magazine maker