Avtron Power Solutions Digital Binder

1

2

3

4

5

6

7

8

30ft CONTAINERISED LOAD BANK & TRANSFORMER PACKAGE

Model 8750 Specifications

A

ELEMENT/FAN MAINTENANCE ACCESS

HV TRANSFORMER (Tx) ACCESS DOOR

LOAD BANK CONTROL ACCESS DOOR

EXHAUST OUTLET FOR Tx COOLING

MAINTENANCE ACCESS

B

2591.0 [102]

B

A

C

5855.0 [230 1

2 ] (TWISTLOCK CENTRES)

2276.0 [89 5 8 ] (MOUNTING BLOCK CENTRES) 2260.0 [89] (TWISTLOCK CENTRES)

PRIMARY HV CABLE ENTRY WITH DIRECT ACCESS TO HV CT's

5880.0 [231 1

2 ] (MOUNTING BLOCK CENTRES)

AIR INLET FOR RESISTIVE ELEMENT COOLING.

120.5 [4 3 4 ]

8922.0 [351 1

4 ] (TWISTLOCK CENTRES)

2438.0 [96]

HV CABLE ACCESS VIA TRANSIT BLOCK SYSTEM SUPPLIED WITH DETACHABLE SHIPPING COVER CUSTOMER TO SUPPLY INDIVIDUAL BLOCKS TO SUIT OWN CABLE SIZES. MORE INFORMATION CAN BE FOUND AT THE SUPPLIERS WEBSITE - www.roxtec.com

8947.0 [352 1

4 ] (MOUNTING BLOCK CENTRES)

218.0 [8 5 8 ]

9125.0 [359 1 4 ]

C

120.5 [4 3 4 ]

120.5 [4 3 4 ]

ADDITIONAL HV CABLE ACCESS

FAN & CONTROL CABLE ACCESS OPENING 242.5x300mm FITTED WITH BLANK ALUMINIUM GLAND PLATE

NOTE: AT LEAST 2 METERS OF CLEAR AREA SHOULD BE LEFT AROUND THE LOAD BANK FOR DOOR OPENINGS AND COOL AIR INLETS

C ( 1 : 30 )

FLOOR ACCESS FOR HV CABLES FITTED WITH BLANK ALUMINIUM GLAND PLATE

A ( 1 : 30 )

1170.0 [46 1 8 ]

B ( 1 : 30 )

3667.5 [144 3 8 ]

300.0 [11 3 4 ]

242.5 [9 1

2 ]

587.5 [23 1 8 ]

3080.0 [121 1 4 ]

400.0 [15 3 4 ]

150.0 [5 7

8 ]

D

400.0 [15 3 4 ]

150.0 [5 7

8 ]

3130.0 [123 1 4 ]

270.0 [10 5 8 ]

716.0 [28 1 4 ]

810.0 [31 7 8 ]

Tx MAINTENANCE ACCESS (IF REQUIRED)

TWISTLOCK FIXINGS AT 20FT PITCH

E

CONTROL CABLE INLET APERTURE CLEAR AREA 400x150mm BLANK ALUMINUM GLAND PLATE

TWISTLOCK FIXINGS AT 30FT PITCH

All dimensions are in millimeters. Specifications subject to change without notice. WEIGHT APPROX - 8750 - 19000kgs

NOTES - ALL LOUVRES ARE MECHANICALLY OPERATED AND WILL OPEN WHEN POWER IS APPLIED TO THE CONTROL CIRCUIT.

REVISION HISTORY

REV

DESCRIPTION

DATE

APPROVED

B

POSITION AND SIZE OF FLOOR APERTURES UPDATED 03/04/2023

MJM

© NJ Froment & Co. Ltd. This document may not be copied or disclosed in whole or partwithout prior written authority.

GENERAL ASSEMBLY 8750 LOAD BANK

CAD Code. Part Number. Drg No.

NJ Froment & Co Ltd Easton on the Hill STAMFORD - PE9 3NP - UK Tel: +44 (0) 1780 480033 avtronpower.com

Drawn - M J Musgrave

Date - 16/11/2021

F

1st Angle Projection

Date -

Checked - Approved -

03756B01

Scale. NTS Dims. mm

Date -

Sheet

1 of 1

Avtron Power Solutions NJ Froment & Co Ltd, Cliffe Road, Easton-on-the-Hill, Stamford, PE9 3NP, UK

www.avtronpower.com customercare@avtronpower.com • +44 (0) 1780 480033 ©2023 Avtron Power Solutions. Publication 5155 • Rev. C

Made with FlippingBook - Online magazine maker